21 kW load bank

Rentaload offers rental of 21 kW air-cooled load banks, designed to operate on three-phase 400 V electrical infrastructure. 

This is an intermediate solution between rack-mountable load banks and high-powered 100/200/300 kW Low Delta T load banks. It is the perfect solution when racks are not yet installed but accurate thermal load distribution must still be validated in the data centre white space. 

The new Smart AC generation has been specifically developed to better match the airflow demand of CRAH units and to respond to real operating conditions where air cooling systems are driven by both pressure difference and temperature variation. 

Its ability to closely match the servers' Delta T capability (10–40 K) is a key advantage, allowing realistic simulation of IT load during data centre commissioning and cooling validation tests. 

In addition, this equipment is designed for ease of handling (small wheels, side handles, lightweight structure). It can easily pass through doors, stairs or ramps, making it ideal for live site environments. 

Benefits and features of the 21 kW load bank

  • Integrated ATS to switch the electrical load between feed A and feed B, without having to disconnect and reconnect cables;
  • Variable Low Delta T (10–40 K) to reproduce real operating conditions in data centre environments and closely match servers’ thermal behaviour;
  • Airflow designed to match CRAH unit demand, allowing realistic simulation when cooling performance is driven by both pressure difference and temperature variation;
  • Integrated circuit breaker to protect both the unit and the electrical installation in case of overcurrent;
  • Up to 20% time savings in carrying out your tests thanks to the connected function of the load bank, allowing remote supervision of an entire fleet of 21 kW units via a supervision PC;
  • Added value brought to your tests thanks to the data collected (P/U/I/Delta T) via the supervision software of your 21 kW connected bench;
  • 1 kW or 3 kW resolution for precise and controlled load adjustment.

The 21 kW charge bank and its connected version

Rentaload offers a connected version of the 21 KW load bank, thanks in particular to its two associated supervision software packages: Rentalab & EkkoSense.

Find out below how to optimize your tests using these 2 connected solutions.

Our Rentalab connected solution

This software allows you to control the entire fleet of connected load banks deployed on site, via a single computer. You can control up to 200 load banks at the same time. You can also collect extremely accurate data such as P/U/I/DELTA T, during testing.

Rentalab is also:

  • Programming of tests up to 72 hours (according to different scenarios);
  • Real-time plotting of supervision curves;
  • Recovery of thermal and electrical information from your tests;
  • Edition of test reports.

The EkkoSense temperature sensor solution

This software allows you to model your computer room in 3D. You can therefore navigate in your room, while collecting thermal data thanks to various wireless temperature sensors positioned in the IT room.

The deployment of this solution includes:

  • Temperature and humidity sensors;
  • An EkkoHub;
  • A 3G connection panel;
  • And all the associated connections, configuration and modeling.

Conclusion

Two different but complementary software programs that allow you to:

  • Save time in carrying out your tests (up to 20% according to feedback from our customers);
  • Bring real added value to your tests. The data collected during the tests provide a real “vital map” of the data centre before its first commissioning.
  • Differentiate yourself from your competitors by enhancing this test phase and providing valuable data for the future management of the datacenter.

Our instrumentation accessories for your 21 kW load bank

Rentaload also offers a number of instrumentation and measurement accessories for hire. They complete the data collected through the software.

  • Thermal camera to analyse the various hot spots in IT rooms;
  • Anemometer to analyse air speed;
  • Analysers to provide network information;
  • Temperature sensors to analyse computer room temperature;
  • Humidity sensors to analyse room humidity;
  • etc

These accessories can be rented independently or in addition to Rentalab and EkkoSense software, depending on your needs.

The temporary containment solution for the 21 kW unit heater load bank

Rentaload offers a temporary containment solution for data centres that do not yet have computer bays. This solution allows you to simulate hot/cold corridors and test the rooms as closely as possible to their subsequent configuration once urbanised.

This gives you the opportunity to test electrical infrastructure and air conditioning systems in parallel.

Our various service offers include the assembly / disassembly of these containment structures if necessary.

Do not hesitate to contact us for more information.

Connection systems for the 21 kW air-cooled load bank

Rentaload adapts to the electrical configuration of each room to be tested. This may involve deploying temporary electrical distribution cabinets to ensure safe and efficient connection of load banks during data centre commissioning and infrastructure testing.

The 210 kW temporary electrical distribution cabinet allows the connection of up to:

  • 10 × 21 kW – 32 A / 400 V load banks
    (or up to 30 rackable 220 V / 32 A load banks)

Connected at the input by 120 mm² cables equipped with Powerlocks, the cabinet can be powered directly from the main electrical panel of the data centre room. Mounted on a metal frame with wheels, it can easily be moved from one room to another, providing flexibility during commissioning phases.

Regarding 21 kW load bank cables, Rentaload offers:

  • P17 32A TRI / P17 32A TRI (tri-tri) cables

Different lengths and cable sections are available to match the technical configuration of each data centre room and ensure safe installation.

More information on the “ cables and accessories ” page.

Technical specifications – 21 kW Smart AC Load Bank

Type Values
Power 21kW
Voltage 400 V – Tri Phases
Resolution 1 kW or 3 kW
Airflow Variable up to 6,000 m³/h
Dual Power Supply Redundancy (100%A – 100%B)
Ventilation Forced horizontal flow
Handling Handles + Wheels + Wooden box storage
Weight 50 Kg
Dimensions Height 900mm
Dimension Width 500mm
Dimension Depth 440mm

Free and without contract

The different types of tests with the 21 kW unit heater load bank

Generator set test

You wish to test your generating set, discover all the specificities of this type of test.

Cooling system test

You want to test your cooling system, discover all the specificities of this type of test.

Test Commissioning

Find out more about Commissioning tests for data centers.

Services associated with the rental of load banks

Support from A to Z

We offer a la carte services.

We can create for you a turnkey service. She understands :

  • delivery of equipment on site,
  • their installations and connections,
  • assistance in carrying out your tests